Dewar LN2-filling compensation with "bank" DHT = 0.105 PMT = 0.075Since May/20, 17:10 CLT:
Dewar LN2-filling compensation moved from the glycol to the air-heater DHT = 0.110Since May/16, 17:10 CLT:
Air: Pa=15.0, Da=5.0 Glycol: Pg=2.0, I=0.3, D=0.0, F=-0.695+0.0370*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.300)/2 DHT = 0.115 PMT = 0.065