PFS Meta Controller

  • Current


    2016 Jun/22-Aug/11

    Since Aug/10:
    Glycol: Pg=2.0, I=0.5, F=-0.475+0.0365*(SetP-Tout)+"GTC"
    adjusted I-term
    

    I don't know what caused the reset of the I-term on Aug/8.
    Someone must have deleted the 'pfs_meta.dat' file on 'guanaco'.

    Since Jul/19:

    Air: Pa=15.0, Da=5.0
    
    Since Jul/11:
    Glycol: Pg=2.0, I=0.5, F=-0.455+0.0365*(SetP-Tout)+"GTC"
    GTC = (glycol_supply-glycol_return-0.314)/2
    
    Since Jul/08:
    Glycol: Pg=2.0, I=1.0, F=-0.450+0.0365*(SetP-Tout)+"GTC"
    GTC = (glycol_supply-glycol_return-0.315)/2
    
    Since Jul/06:
    Glycol: Pg=2.0, I=2.0, F=-0.465+0.0365*(SetP-Tout)+"GTC"
    GTC = (glycol_supply-glycol_return-0.310)/2
    
    Since Jul/01 9:00 CLT:
    Pato adjusted the PMT-compensation potentiometer from 208 to 240 Ohms.
    
    Since Jun/28 15:30 CLT:
    Pato adjusted the PMT-compensation potentiometer from 122 to 208 Ohms.
    Glycol: Pg=2.0, I=2.0, F=-0.545+0.0365*(SetP-Tout)+"GTC"
    
    Since Jun/23:
    Glycol: Pg=2.0, I=0.5, F=-0.545+0.0365*(SetP-Tout)+"GTC"
    GTC = (glycol_supply-glycol_return-0.305)/2
    I-term -= 0.0025
    
    Since Jun/20:
    Air: Pa=12.0, Da=3.0
    Glycol: Pg=2.0, I=0.5, F=-0.550+0.0365*(SetP-Tout)+"GTC"
    GTC = (glycol_supply-glycol_return-0.300)/2