Glycol: Pg=2.0, I=0.5, F=-0.475+0.0365*(SetP-Tout)+"GTC" adjusted I-term
Since Jul/19:
Air: Pa=15.0, Da=5.0Since Jul/11:
Glycol: Pg=2.0, I=0.5, F=-0.455+0.0365*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.314)/2Since Jul/08:
Glycol: Pg=2.0, I=1.0, F=-0.450+0.0365*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.315)/2Since Jul/06:
Glycol: Pg=2.0, I=2.0, F=-0.465+0.0365*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.310)/2Since Jul/01 9:00 CLT:
Pato adjusted the PMT-compensation potentiometer from 208 to 240 Ohms.Since Jun/28 15:30 CLT:
Pato adjusted the PMT-compensation potentiometer from 122 to 208 Ohms. Glycol: Pg=2.0, I=2.0, F=-0.545+0.0365*(SetP-Tout)+"GTC"Since Jun/23:
Glycol: Pg=2.0, I=0.5, F=-0.545+0.0365*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.305)/2 I-term -= 0.0025Since Jun/20:
Air: Pa=12.0, Da=3.0 Glycol: Pg=2.0, I=0.5, F=-0.550+0.0365*(SetP-Tout)+"GTC" GTC = (glycol_supply-glycol_return-0.300)/2